Specifications UPS ICA RN 2400C
|
Description |
UPS RN2400C |
|
Capacity |
2400 VA / 1200 W |
|
AC Voltage |
160 – 250 V |
|
AC Frequency |
50 ± 3 Hz |
|
AC Protection |
10 A |
|
DC Voltage |
72 V |
|
DC INT Battery |
6 x 12 V, 7 Ah |
|
DC Protection |
FUSE |
|
CHG Topology |
SWITCHING REGULATION |
|
CHG Floating Voltage |
81.6 V |
|
INV Wave Form |
SINEWAVE |
|
INV Distorsion |
< 3% THD |
|
INV Topology |
PULSE WIDTH MODULATION (PWM) |
|
INV Voltage |
220 ± 2% V |
|
INV Frequency |
50 Hz |
|
INV Efficiency |
> 85% |
|
Transfer Time AC FAIL |
0 ms |
|
Transfer Time STS |
2 ms INVERTER TO BYPASS |
|
ZERO CROSSING BYPASS TO INVERTER |
|
|
Back Up Time |
10 min |
|
BZR AC IN ABNORMAL |
INTERMITTENT SOUND WITH 4 SECONDS INTERVAL |
|
BZR Battery Low |
INTERMITTENT SOUND WITH 1 SECONDS INTERVAL |
|
Opera Temp |
0 – 40 °C |
|
Dimension(DxWxH) |
550 x 435 x 176 mm |
|
Weight |
35 Kg |


Review